Esco 10 DL40 - Pressurized Steam Humidifier in Stainless Steel with 3x Pipe
Condair

Esco 10 DL40 - Pressurized Steam Humidifier in Stainless Steel with 3x Pipe

The Condair Esco uses steam from a building’s existing steam network to provide humidification to an air handling unit (AHU) or duct. It conditions the steam to remove condensation and ensures that only dry steam is delivered for humidity control.

Condair Esco 10 DL40 can operate at up to 4 bar and provide up to 250 kg/hr of humidification to an AHU. It incorporates a ceramic rotary disc valve that offers 0-100% modulation, very close control and prevents the possibility of steam leakage when closed.

The Condair Esco’s steam pipe has tiny inner nozzles that draw steam only from the centre of the steam pipe, where it is at its hottest and driest. This ensures that any condensation that occurs around the cooler outer edges is not introduced to the duct.

Unlike other pressurized steam humidifiers that incorporate pre-heated steam lances to avoid this “spitting”, the Esco’s steam pipe reduces heat transfer to the air stream and provides instant humidity on demand without any pre-heating time needed.

The Condair Esco is available with ductile cast iron or stainless steel valve units and with a variety of steam pipe options to suit duct dimensions and satisfy required humidification (absorption) distances.

Cпецификация
  • Condair Esco DL40 - with 3x steam pipes

    This is a configured product. Please contact your Condair partner for a selection according to your air handling unit or duct dimensions and the required humidity.

    Take care about the humidification distance downstream of the steam pipe. This distance is variable and depends on the given air conditions on site. Therefore, it's not possible to show this kind of clearance in the files directly. The humidification distance must be handled like a clearance. No obstacles can be placed within this distance.

    Esco 10 - DL40 Triple Pipe Type Overview

    • Admissible steam over pressure: 0.2 ... 4.0 bar
    • Min. required air handling unit / duct height: 1000 mm

    Collector Dimensions:

    • 250 mm, 300 mm, 600 mm or 900 mm distance between the steam pipes available

    Collector max. admissible steam capacity [kg/h]

    • 116
    • 211
    • 250

    The collector type max. steam capacity must be higher, than the present steam capacity.

    Type 3-10/023:

    • Max. Steam Capacity 48 kg/h
    • Air Handling Unit (AHU) / Duct width: 250 ... 399 mm
    • Required Collector Capacity 116 kg/h

    Type 3-10/038:

    • Max. Steam Capacity 81 kg/h
    • Air Handling Unit (AHU) / Duct width: 400 ... 499 mm
    • Required Collector Capacity 116 kg/h

    Type 3-10/048:

    • Max. Steam Capacity 96 kg/h
    • Air Handling Unit (AHU) / Duct width: 500 ... 599 mm
    • Required Collector Capacity 116 kg/h

    Type 3-10/058:

    • Max. Steam Capacity 123 kg/h
    • Air Handling Unit (AHU) / Duct width: 600 ... 699 mm
    • Required Collector Capacity 116 or 211 kg/h, depends on the present steam capacity

    Type 3-10/068:

    • Max. Steam Capacity 150 kg/h
    • Air Handling Unit (AHU) / Duct width: 700 ... 899 mm
    • Required Collector Capacity 116 or 211 kg/h, depends on the present steam capacity

    Type 3-10/088:

    • Max. Steam Capacity 186 kg/h
    • Air Handling Unit (AHU) / Duct width: 900 ... 1199 mm
    • Required Collector Capacity 116 or 211 kg/h, depends on the present steam capacity

    Type 3-10/118:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 1200 ... 1499 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/148:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 1500 ... 1799 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/178:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 1800 ... 2099 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/208:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 2100 ... 2399 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/238:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU)/ Duct width: 2400 ... 2699 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/268:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 2700 ... 2998 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/298:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 3000 ... 3299 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/328:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 3300 ... 3599 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/358:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 3600 ... 3899 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/388:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 3900 ... 4299 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity
Техническая спецификация
  • Уникальная ссылкаcondair-esco-10-dl40-3-pipe-stainless-steel
  • Тип продукцииAir Humidifier
  • Группа продукцииPressurized Steam Humidifier
  • ТипОбъект (один объект)
  • Дата публикации2023-05-19
  • Номер версии1
Ссылки
Связанные
  • Основной материалНержавеющая сталь
  • Разработано вШвейцария
  • Страна-производительГермания
Классификация
  • Категория BIMobjectВентиляция и кондиционирование воздуха - Вентиляция и кондиционирование воздуха
  • Классификация IFCУвлажнитель
  • Код ETIMEC011628
  • Название ETIMHumidifier (steam)
  • Название по ССКПУ ООНHumidifiers
  • Код ССКПУ ООН40101903
  • Код Uniclass 2015Pr_65_67_39_84
  • Описание Uniclass 2015Steam humidifiers
  • Код CSI MasterFormat 201423 84 13.23
  • Заголовок CSI MasterFormat 2014Direct-Steam-Injection Humidifiers
  • Номер OmniClass23-33 27 15
  • Наименование OmniClassAir Humidifiers
  • Код CSI UniFormat IID3090
  • Заголовок CSI UniFormat IIOther HVAC Systems & Equipment

Доступно в регионах:

Азия Африка Южная Америка Европа Океания
Израиль
Ангола
Аргентина
Австрия
Австралия
Индия
Ботсвана
Уругвай
Бельгия
Новая Зеландия
Индонезия
Египет
Чили
Болгария
Иордания
Зимбабве
Великобритания
Китай
Мозамбик
Венгрия
Малайзия
Намибия
Германия
Объединенные Арабские Эмираты
Тунис
Греция
Пакистан
Южная Африка
Дания
Саудовская Аравия
Ирландия
Сингапур
Исландия
Сирия
Испания
Таиланд
Италия
Турция
Латвия
Южная Корея
Литва
Нидерланды
Норвегия
Польша
Португалия
Румыния
Сербия
Словакия
Словения
Украина
Финляндия
Франция
Хорватия
Чехия
Швейцария
Швеция
Эстония