FireCoil Features and Options
Every Raynor FireCoil fire-rated rolling door is built for superior performance and includes the features and options listed below:
Safety
Doors of all sizes meet NFPA 80 requirements. Closing speed is consistently controlled between 6-12” per second, resulting in a more smooth, quiet, and safer descent.
Savings
The state-of-the-art design incorporates automatic resetting of the auto-closing system. All doors can be easily reset with a single-side release which results in dramatic savings in testing and resetting costs while minimizing downtime.
Fusible Link
Automatic door closure is initiated by one of three fusible links that melt at 165° Fahrenheit.
Pre-Assembled Rolling Steel Door
Our Raynor pre-assembled rolling steel door option allows for faster and easier installation by having the curtain, barrel, and head plates shipped pre-assembled and in one crate. Ask your Raynor Authorized Dealer how to take advantage of our pre-assembled option.
Bottom Bar
Curtain bottoms are reinforced with a minimum of two steel angles for maximum durability. A bottom astragal is included on all motor-operated doors.
Curtain
All FireCoil door curtains are constructed with heavy-duty steel slats: Flat Slats (UF), Insulated Flat Slats (UI), Large Contour Slats (LL), and Small Contour Slats (US). See the Slat Style Options tab below.
Counterbalance System
A torsion-spring-operated system, enclosed in a structural steel barrel, effectively counterbalances the FireCoil fire-rated door for a minimum of 10,000 cycles.
Guides and End Locks
Steel angle guides provide added support for curtain slats. Zinc-plated, malleable cast-iron end locks prevent lateral movement of the curtain slats.
Locks
In applications where control and access are important, choose from a variety of locking options to help keep your building secure. Locks come in either cylinder or slide-bolt (shown) variations. Slide-bolt locks are standard on push-up operation.
Curtain Hood*
For maximum structural rigidity, curtain hoods feature rolled edges and are formed from 24 gauge, hot-dipped galvanized steel.
*FireCoil hood includes a flame baffle that is activated by a fusible link. Standard on Factory Mutual-approved doors. Optional on UL-approved doors.
Smoke Control
A guide with a brush seal (shown) and header seal reduce smoke damage.