Approvals: Power Supply Approvals: UL 294 (6th Edition) listed, UL 603 listed, UL 1481 listed, ULC-S318 listed
Call Station Options: Indoor Flush Mount Model: AOR-CSE-FM, Indoor Surface Mount Model: AOR-CSE-SM
Communication: Lighted phone with 12-button keypad receives and selectively originates calls
Connectivity: Supports one (1) analog phone line (PSTN line) per bank of 8-stations for off-site dialing (total of four (4) PSTN lines)
Environment: For indoor use
Fault Monitoring: Activation of any AOR Station, opens/shorts on AOR Station cabling, 110VAC input power failure (primary power loss), low battery backup (low voltage detected), and system ground fault
Mounting: Surface mount or recess mount with optional trim ring (Model AOR-TR32). Strobe/sounder mounts to standard 4-inch square box.
Power: 120VAC, 1.0 A (max)
Supervision Relay: Activation of Any AOR Station: Contact closure (relay) output; Open/Short Fault on AOR Stations: Contact closure (relay) output; AC Input Power Failure: 24VDC output; Low Battery (Low Voltage Detected): Form C output; and System Ground Fault: Contact closure (relay) output.
Wiring: One (1) twisted, shielded pair per station not to exceed 25 ohms resistance
Keywords: two way emergency communication, emergency panel, emergency response panel, emergency panel alarm, emergency communication system