Airflow Measuring Station - Thermal Dispersion - Steel Airfoil Parallel Blade - AM-45-TD

Airflow Measuring Station - Thermal Dispersion - Steel Airfoil Parallel Blade - AM-45-TD

Airflow Measuring Station
Steel Airfoil - Thermal Dispersion

AM-45-TD airflow measuring stations employ a low leakage control damper with highly accurate airflow measuring equipment in a single compact assembly. The Pottorff CD-45 control damper is factory mounted with a modulating 24V actuator and thermal dispersion airflow measurement system to provide airflow measuring along with the ability to control airflow all in one easy to install assembly. Fully encapsulated precision thermistors are paired with heating circuits and dedicated ELECTRA-flo G5 transmitters to provide a high degree of environmental protection along with state-of-the electronic airflow measurement.

Specificatie
  • Standard Construction

    Damper Frame: 5" x 1" (127 x 25) galvanized steel hat channel with interlocking corner gusset. Equivalent to 13 gauge 92.4) channel frame. Low profile head and sill are used on sizes less than 13" (330) high.

    Damper Blades: 6" x 14" gauge (152 x 2.0) equivalent galvanized steel - airfoil. Parallel.

    Sleeve: 16" x 20 gauge (406 x 1.0) galvanized steel.

    Damper Axles: 1/2" (13) diameter plated steel hex.

    Damper Linkage: Concealed in frame.

    Damper Bearings: Synthetic.

    Seals: Silicone blade edge seals integrally rolled and mechanically fastened to blades. Flexible metal jamb seals.

    Damper Actuator: Modulating 24V, spring close, external mount.

    Transmitter: ELECTRA-flo G5 with NEMA 1 enclosure.

    Minimum Size: 8" x 6" (2-3 x 152)

    Maximum Size:
    Single Section: 48" x 72" (1219 x 1829)
    Multiple Section: 120" x 120" (3048 x 3048)


    Ratings

    System Velocity Range: 0-4000 fpm (0-20.32 m/s)

    Maximum System Pressure: 2 in. wg. (0.50 kPa)

    Leakage:
    3.0 cfm/ft2 @ 1.0 in. wg. (0.015 m3/s/m2 @ 0.25 kPa)
    4.0 cfm/ft2 @ 1.0 in. wg. (0.02 m3/s/m2 @ 0.25 kPa)
    8.0 cfm/ft2 @ 4.0 in. wg. (0.041 m3/s/m2 @ 1.0 kPa)
    9.7 cfm/ft2 @ 6.0 in. wg. (0.049 m3/s/m2 @ 1.5 kPa)

Technische specificatie
  • Unieke ref.Airflow-Measuring-Station-Thermal-Dispersion-Steel-Airfoil-Parallel-Blade-AM-45-TD
  • ProductfamilieHVAC
  • ProductgroepAir Control Dampers
  • TypeObject (enkelvoudig object)
  • Publicatiedatum2024-07-16
  • Editienummer1
Classificatie
  • Categorie BIMobjectHVAC-apparatuur - Mechanische ventilatie
  • Uniclass 2015-codeSs_75_70_96_30
  • Uniclass 2015-beschrijvingFlow measurement and control systems
  • CSI MasterFormat 2014 Code40 71 00
  • CSI MasterFormat 2014 TitelFlow Measurement
  • OmniClass-nummer23-27 11 15
  • OmniClass-titelFlow Measuring Instrument And Controls

Beschikbaarheid regio

Noord Amerika
Amerikaanse Maagdeneilanden
Anguilla
Antigua en Barbuda
Aruba
Bahama's
Barbados
Belize
Bermuda
Britse Maagdeneilanden
Canada
Caribisch Nederland
Costa Rica
Cuba
Curaçao
Dominica
Dominicaanse Republiek
El Salvador
Grenada
Groenland
Guadeloupe
Guatemala
Haïti
Honduras
Jamaica
Kaaimaneilanden
Martinique
Mexico
Montserrat
Nicaragua
Panama
Porto Rico
Saint Kitts en Nevis
Saint Martin
Saint Vincent en de Grenadines
Saint-Barthélemy
Saint-Pierre en Miquelon
SaintLucia
Sint Maarten
Trinidad en Tobago
Turks- en Caicoseilanden
Verenigde Staten

Soortgelijke producten