제품 게시
Esco 10 DL40 - Pressurized Steam Humidifier in Stainless Steel with 3x Pipe
Condair

Esco 10 DL40 - Pressurized Steam Humidifier in Stainless Steel with 3x Pipe

The Condair Esco uses steam from a building’s existing steam network to provide humidification to an air handling unit (AHU) or duct. It conditions the steam to remove condensation and ensures that only dry steam is delivered for humidity control.

Condair Esco 10 DL40 can operate at up to 4 bar and provide up to 250 kg/hr of humidification to an AHU. It incorporates a ceramic rotary disc valve that offers 0-100% modulation, very close control and prevents the possibility of steam leakage when closed.

The Condair Esco’s steam pipe has tiny inner nozzles that draw steam only from the centre of the steam pipe, where it is at its hottest and driest. This ensures that any condensation that occurs around the cooler outer edges is not introduced to the duct.

Unlike other pressurized steam humidifiers that incorporate pre-heated steam lances to avoid this “spitting”, the Esco’s steam pipe reduces heat transfer to the air stream and provides instant humidity on demand without any pre-heating time needed.

The Condair Esco is available with ductile cast iron or stainless steel valve units and with a variety of steam pipe options to suit duct dimensions and satisfy required humidification (absorption) distances.

사양
  • Condair Esco DL40 - with 3x steam pipes

    This is a configured product. Please contact your Condair partner for a selection according to your air handling unit or duct dimensions and the required humidity.

    Take care about the humidification distance downstream of the steam pipe. This distance is variable and depends on the given air conditions on site. Therefore, it's not possible to show this kind of clearance in the files directly. The humidification distance must be handled like a clearance. No obstacles can be placed within this distance.

    Esco 10 - DL40 Triple Pipe Type Overview

    • Admissible steam over pressure: 0.2 ... 4.0 bar
    • Min. required air handling unit / duct height: 1000 mm

    Collector Dimensions:

    • 250 mm, 300 mm, 600 mm or 900 mm distance between the steam pipes available

    Collector max. admissible steam capacity [kg/h]

    • 116
    • 211
    • 250

    The collector type max. steam capacity must be higher, than the present steam capacity.

    Type 3-10/023:

    • Max. Steam Capacity 48 kg/h
    • Air Handling Unit (AHU) / Duct width: 250 ... 399 mm
    • Required Collector Capacity 116 kg/h

    Type 3-10/038:

    • Max. Steam Capacity 81 kg/h
    • Air Handling Unit (AHU) / Duct width: 400 ... 499 mm
    • Required Collector Capacity 116 kg/h

    Type 3-10/048:

    • Max. Steam Capacity 96 kg/h
    • Air Handling Unit (AHU) / Duct width: 500 ... 599 mm
    • Required Collector Capacity 116 kg/h

    Type 3-10/058:

    • Max. Steam Capacity 123 kg/h
    • Air Handling Unit (AHU) / Duct width: 600 ... 699 mm
    • Required Collector Capacity 116 or 211 kg/h, depends on the present steam capacity

    Type 3-10/068:

    • Max. Steam Capacity 150 kg/h
    • Air Handling Unit (AHU) / Duct width: 700 ... 899 mm
    • Required Collector Capacity 116 or 211 kg/h, depends on the present steam capacity

    Type 3-10/088:

    • Max. Steam Capacity 186 kg/h
    • Air Handling Unit (AHU) / Duct width: 900 ... 1199 mm
    • Required Collector Capacity 116 or 211 kg/h, depends on the present steam capacity

    Type 3-10/118:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 1200 ... 1499 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/148:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 1500 ... 1799 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/178:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 1800 ... 2099 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/208:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 2100 ... 2399 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/238:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU)/ Duct width: 2400 ... 2699 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/268:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 2700 ... 2998 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/298:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 3000 ... 3299 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/328:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 3300 ... 3599 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/358:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 3600 ... 3899 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity

    Type 3-10/388:

    • Max. Steam Capacity 250 kg/h
    • Air Handling Unit (AHU) / Duct width: 3900 ... 4299 mm
    • Required Collector Capacity 116, 211 or 250 kg/h, depends on the present steam capacity
기술 사양
  • 특징 참조condair-esco-10-dl40-3-pipe-stainless-steel
  • 제품군Air Humidifier
  • 제품분류Pressurized Steam Humidifier
  • 유형개체 (단일 개체)
  • 게시일2023-05-19
  • 에디션 넘버1
관련성
  • 주 재료스테인레스강
  • 설계국가스위스
  • 제조국가독일
분류
  • BIMobject 카테고리HVAC - HVAC
  • IFC 분류가습기
  • ETIM 코드EC011628
  • ETIM 이름Humidifier (steam)
  • UNSPSC 이름Humidifiers
  • UNSPSC 코드40101903
  • Uniclass 2015 코드Pr_65_67_39_84
  • Uniclass 2015 설명Steam humidifiers
  • CSI 마스터 형식 2014 코드23 84 13.23
  • CSI 마스터 형식 2014 제목Direct-Steam-Injection Humidifiers
  • OmniClass 번호23-33 27 15
  • OmniClass 제목Air Humidifiers
  • CSI 단일 형식 II 코드D3090
  • CSI 단일 형식 II 제목Other HVAC Systems & Equipment

지역 가용성

아시아 아프리카 남아메리카 유럽 오세아니아
대한민국
나미비아
아르헨티나
그리스
뉴질랜드
말레이시아
남아프리카
우루과이
네덜란드
오스트레일리아
사우디아라비아
모잠비크
칠레
노르웨이
시리아
보츠와나
덴마크
싱가포르
앙골라
독일
아랍에미레이트
이집트
라트비아
요르단
짐바브웨
루마니아
이스라엘
튀니지
리투아니아
인도
벨기에
인도네시아
불가리아
중국
세르비아
태국
스웨덴
터키
스위스
파키스탄
스페인
슬로바키아
슬로베니아
아이슬란드
아일랜드
에스토니아
영국
오스트리아
우크라이나
이탈리아
체코 공화국
크로아티아
포르투갈
폴란드
프랑스
핀란드
헝가리