Condair Esco 10 DL40 - with 2x steam pipe
This is a configured product. Please contact your Condair partner for a selection according to your air handling unit or duct dimensions and the required humidity.
Take care about the humidification distance downstream of the steam pipe. This distance is variable and depends on the given air conditions on site. Therefore, it's not possible to show this kind of clearance in the files directly. The humidification distance must be handled like a clearance. No obstacles can be placed within this distance.
Accessories shown in the models:
- Electric Actuator Condair CA150A-MP
- Steam Trap Spirax Sarco: Type Ball Float and Thermostatic
- Pressure Gauge
Esco 10 - DL40 Double Pipe Type Overview
- Admissible steam over pressure: 0.2 ... 4.0 bar
- Min. required air handling unit / duct height: 700 mm
Collector Dimensions:
- 250 mm, 300 mm, 600 mm or 900 mm distance between the steam pipes available
Collector Type max. admissible steam capacity [kg/h]
The collector type max. steam capacity must be higher, than the present steam capacity.
Type 2-10/023:
- Max. Steam Capacity 32 kg/h
- Air Handling Unit (AHU) / Duct width: 250 ... 399 mm
- Collector Type 116
Type 2-10/038:
- Max. Steam Capacity 54 kg/h
- Air Handling Unit (AHU) / Duct width: 400 ... 499 mm
- Collector Type 116
Type 2-10/048:
- Max. Steam Capacity 64 kg/h
- Air Handling Unit (AHU) / Duct width: 500 ... 599 mm
- Collector Type 116
Type 2-10/058:
- Max. Steam Capacity 82 kg/h
- Air Handling Unit (AHU) / Duct width: 600 ... 699 mm
- Collector Type 116
Type 2-10/068:
- Max. Steam Capacity 100 kg/h
- Air Handling Unit (AHU) / Duct width: 700 ... 899 mm
- Collector Type 116
Type 2-10/088:
- Max. Steam Capacity 124 kg/h
- Air Handling Unit (AHU) / Duct width: 900 ... 1199 mm
- Collector Type 116 or 211, depends on the present steam capacity
Type 2-10/118:
- Max. Steam Capacity 188 kg/h
- Air Handling Unit (AHU) / Duct width: 1200 ... 1499 mm
- Collector Type 116 or 211, depends on the present steam capacity
Type 2-10/148:
- Max. Steam Capacity 236 kg/h
- Air Handling Unit (AHU) / Duct width: 1500 ... 1799 mm
- Collector Type 116, 211 or 250, depends on the present steam capacity
Type 2-10/178:
- Max. Steam Capacity 250 kg/h
- Air Handling Unit (AHU) / Duct width: 1800 ... 2099 mm
- Collector Type 116, 211 or 250, depends on the present steam capacity
Type 2-10/208:
- Max. Steam Capacity 250 kg/h
- Air Handling Unit (AHU) / Duct width: 2100 ... 2399 mm
- Collector Type 116, 211 or 250, depends on the present steam capacity
Type 2-10/238:
- Max. Steam Capacity 250 kg/h
- Air Handling Unit (AHU)/ Duct width: 2400 ... 2699 mm
- Collector Type 116, 211 or 250, depends on the present steam capacity
Type 2-10/268:
- Max. Steam Capacity 250 kg/h
- Air Handling Unit (AHU) / Duct width: 2700 ... 2998 mm
- Collector Type 116, 211 or 250, depends on the present steam capacity
Type 2-10/298:
- Max. Steam Capacity 250 kg/h
- Air Handling Unit (AHU) / Duct width: 3000 ... 3299 mm
- Collector Type 116, 211 or 250, depends on the present steam capacity
Type 2-10/328:
- Max. Steam Capacity 250 kg/h
- Air Handling Unit (AHU) / Duct width: 3300 ... 3599 mm
- Collector Type 116, 211 or 250, depends on the present steam capacity
Type 2-10/358:
- Max. Steam Capacity 250 kg/h
- Air Handling Unit (AHU) / Duct width: 3600 ... 3899 mm
- Collector Type 116, 211 or 250, depends on the present steam capacity
Type 2-10/388:
- Max. Steam Capacity 250 kg/h
- Air Handling Unit (AHU) / Duct width: 3900 ... 4299 mm
- Collector Type 116, 211 or 250, depends on the present steam capacity