FT-3400 Insertion Electromagnetic Flow Meter

FT-3400 Insertion Electromagnetic Flow Meter

ONICON's FT-3400 Series Insertion Electromagnetic Flow Meters are suitable for measuring electrically conductive liquids in a wide variety of applications. Each FT-3400 provides a single analog output for flow rate, a high resolution frequency output to drive peripheral devices, a scalable pulse output for totalization, and an empty pipe alarm. It is available for use in pipes ranging in size from 1¼" to 72" in diameter. The FT-3400 Insertion Electromagnetic Flow Meter features ONICON's unique hot tap design that allows for easy insertion or removal from the pipe without the use of special tools and without disrupting flow. The low maintenance design is provided ready-to-use without the need for field programming. 

Typical Applications

The FT-3400 is ideal for chilled water, hot water, domestic water, condenser water and municipal water applications.

Standard Features

Highly Accurate - Each flow meter is individually wet calibrated and accurate to within ± 1.0% of reading.

Simple Installation and Commissioning - Each flow meter is factory programmed and ready for use upon delivery.

Low Maintenance - No moving parts and durable construction provide years of maintenance-free service.

Tekniset tiedot
  • Basis of Design: ONICON Model F-3500 Series Insertion Electromagnetic Flowmeter. Manufacturers approved to bid, subject to compliance with requirements include:

    Insert additional MFG’s pre-approved to bid.

    Description: Provide an insertion electromagnetic flowmeter complete with NIST traceable, wet calibrated flow-measuring element, integral transmitter, installation valves, installation depth gage and calibration certificate. Flowmeter shall be wet tappable, allowing insertion and removal from the flow stream without system shutdown.

    Application Range: This contractor shall be responsible for selecting the flowmeter options submitted based on the application, refer to section for 230519.3.4 “Flowmeter Schedule by Application”. Flowmeter shall be constructed, calibrated and scaled for the intended application in terms of pipe size, pipe material, installation requirements, expected flow rate, ambient conditions and fluid characteristics which include but are not limited to pressure, temperature, conductivity and viscosity.

    Sensing Technology: Electromagnetic velocity-measuring element.

    Design: Electromagnetic sensing element shall utilize two sets of diametrically opposed electrodes to measure the average flow rate velocity.

    Construction: Wetted components shall be constructed of 316L stainless steel with attached tag indicating calibration information.

    Maximum Pressure Rating: 400 psig.

    Maximum Temperature Rating: 200 deg F.

    End Connections for NPS 1.25” and Larger: 1” Male NPT Hot Tap Adapter fitting. Installation through 1” full port isolation valve, minimum.

    Flow Range: Flow-measuring element and transmitter shall cover operating range of equipment or system served.

    Accuracy: Flowmeter shall provide calibrated outputs directly from the integral transmitter, throughout the operating range with the accuracy stated as follows:

    Plus or minus 1.0% of rate from 2.0 to 20.0 ft/sec velocity (10:1 turndown).

    Plus or minus 0.02 ft/sec below 2 ft / sec

    Calibration: Each flowmeter shall receive a wet calibration, within the expected operating range, against a primary volumetric standard that is traceable to NIST.

    Optional Local Display: Local display shall provide instantaneous flow rate information and totalized flow information and shall be factory configured for connection to a specific flowmeter.

    Operating and Installation Instructions: Installation and operating instructions shall be provided for each flowmeter. Refer to section 230519.3.4 “Flowmeter Schedule by Application” for additional installation requirements.

    Warranty: Each flowmeter shall be covered by the manufacturer’s three-year warranty.

Tekniset tiedot
  • Yksilöity viiteft-3400-series-insertion-electromagnetic-flow-meter
  • TuoteperheFlow and Energy Measurement
  • TuoteryhmäElectromagnetic Flow Meters
  • TyyppiObjekti (yksittäinen objekti)
  • Julkaisupäivä2023-11-02
  • Painoksen numero1
Liittyviä
  • Suunniteltu:Yhdysvallat
  • Valmistettu:Yhdysvallat
Luokitus
  • BIMobject-luokkaLVI - LVI
  • ETIM-koodiEC010582
  • ETIM-nimiElectromagnetic liquid flow meter
  • Uniclass 2015 -koodiPr_80_51_46_27
  • Uniclass 2015 -kuvausElectromagnetic flow meters
  • CSI MasterFormat 2014 -koodi40 71 00
  • CSI MasterFormat 2014 -nimikeFlow Measurement
  • OmniClass-numero23-27 11 15
  • OmniClass-nimikeFlow Measuring Instrument And Controls

Alueellinen saatavuus

Pohjois-Amerikka
Anguilla
Antigua ja Barbuda
Aruba
Bahamasaaret
Barbados
Belize
Bermuda
Brittiläiset Neitsytsaaret
Caribbean Netherlands
Caymansaaret
Costa Rica
Curaçao
Dominica
Dominikaaninen tasavalta
El Salvador
Grenada
Grönlanti
Guadeloupe
Guatemala
Haiti
Honduras
Jamaika
Kanada
Kuuba
Martinique
Meksiko
Montserrat
Nicaragua
Panama
Puerto Rico
Saint Kitts ja Nevis
Saint Lucia
Saint Vincent ja Grenadiinit
Saint-Barthélemy
Saint-Martin
Saint-Pierre ja Miquelon
Sint Maarten
Trinidad ja Tobago
Turks- ja Caicossaaret
Yhdysvallat
Yhdysvaltain Neitsytsaaret