Curtain:
Barrel with 1.5 mm thick glass filament fabric reinforced with V4A wire, coated with intumescent graphite on both sides
1750 g/m², temperature-resistant up to 1100 degrees, bottom strip as closing weight
Motor:
Tubular drive 230 V/50 Hz, 265 to 430 W
Integrated hold-open device with asbestos-free brake pad (24 V),
Integrated centrifugal brake limits speed in case the door fabric rolls due to gravity,
5-metre connecting lead Ölflex Servo FD 796P, cable end insulated and fitted with ferrules,
2x 0.5-m connecting lead with plug for the magnetic contacts of end-of-travel position monitoring,
Application range -10 °C to +50 °C
Control
FSA FlexControl control unit with membrane keypad and integrated status displays,
Motorised curtain opening, closing via closing weight upon detection of smoke, button actuation or power failure.
Side guide
Double-shell guide rail, optionally in RAL to choose with integrated magnetic contact for travel limit.
Fitting
NOTE:
Classification EW prevents fire from spreading for the specified duration. Fire protection curtains with this classification reduce the radiation heat according to 13501-2.
Classification EW does not correspond to a product with T30, T90 or EI230, EI290 classification.
Fitting prerequisites:
Brickwork
Fire-proof walls made of brickwork and bricks with minimum strength class 12, standard mortar of mortar group ≥ II
Min.: 175 mm
Concrete:
Fire-proof walls made of concrete, min. strength class C12/15
Min.: 140 mm
Partition wall:
Fire-proof partition walls (base acc. to statics requirements) acc. to EN 1363-1
Min. 135 mm
Steel components:
Fire-proof encased steel components (constructed acc. to statics requirements)
REI 30 - REI 120
Application areas: Commercial construction, administrative buildings, hospital construction, fire protection