RTL 120 is the unit (SLAVE) of the Multizone System for the control of heating and other functions in a single zone. 

  • Housed in a standard built-in 503 enclosure  (it is compatible with the switchboards and plates commonly on sale).
  • Receives power from an auxiliary power supply
  • Controls the local thermal units by means of:
    • On-Off zone valve with 230 V~ actuator and modulation unit with 0...10 Volt – input
    • On-Off zone valve with 24 V~ (or other voltages) actuator, and modulation unit with 0...10 Volt – input
    • Zone valve with 24 V~ (or other voltages) thermal actuator, and modulation unit with 0...10 Volt – input
    • Fixed or variable speed zone circulation pump
    • Zone burner or small boiler with 0...10 Volt – input in POWER or TEMPERATURE
    • On-Off valve and fan-coil ventilator switch with 0...10 Volt – input
    • Any other device that can be controlled via a three-point relay and with 0...10 Volt input –
  • Room sensor (internal or external)
  • Complete configuration of the limits and mode of use permitted to user
  • Three On-Off inputs to be programmed as required
  • Large display with simplified readout 
  • Three operational push-button switches with “intuitive” use 
  • Ability to work even in case of breakdown of the communication with the central unit
  • Customisable unit name 
Tekniset tiedot
    • Power supply: 13 V –
    • Maximum consumption: 30 milliWatt
    • Voltage-free output contacts:
      • maximum switched voltage 250 V ~
      • maximum switched current 5 (1) A
    • Protection: IP40
    • Ambient temperature:
      • operating 0 … 45°C
      • storage – 25 … + 60°C
    • Ambient humidity class: F DIN 40040
    • Internal or remote room sensor
      • Measurement range: 0 … + 50 °C
      • Sensor error: +/– 0.3 °C
    • 1 Relay for selection heating/conditioning 
    • 1 0...10 Volt output
      • Maxiumum input load: 1mA 
      • Min. and Max. limits can be set on the Master unit
    • 3 Programmable auxiliary inputs, with the following acquisition time:
      • Switch minimum: 300 msec
      • Button minimum: 150 msec.
    • Programs Heating/Condit. for individual zones
      • 24hour programs: 1 … 7
        • 24hour times: 6
      • Weekly programs: 0 …7
      • Programs with limited time (P. LIMIT): 1
        • Maximum time limited to 7 days & 23 hours
      • Annual programs: 1...5
    • All the alarm functions are available in order to have instantaneous control of the zone situation
    • Management by Master Via P-Loc Bus
Tekniset tiedot
  • Yksilöity viitecostergroup-rtl120
  • TuoteperheMULTIZONE SYSTEM
  • TuoteryhmäHEATING
  • TyyppiObjekti (yksittäinen objekti)
  • Julkaisupäivä2020-03-11
  • Painoksen numero1
  • Korkeus (mm)50
  • Leveys (mm)92
  • Syvyys (mm)39.5
Liittyviä
  • Ensisijainen materiaaliABS
  • Toissijainen materiaaliNailon
  • Suunniteltu:Italia
  • Valmistettu:Italia
Luokitus
  • BIMobject-luokkaLVI - Ohjauspaneelit

Alueellinen saatavuus

Eurooppa
Ahvenanmaa
Alankomaat
Albania
Andorra
Belgia
Bosnia ja Hertsegovina
Bulgaria
Espanja
Färsaaret
Gibraltar
Guernsey
Huippuvuoret
Irlanti
Islanti
Italia
Itävalta
Jersey
Kreikka
Kroatia
Kypros
Latvia
Liechtenstein
Liettua
Luxemburg
Malta
Mansaari
Moldova
Monaco
Montenegro
Norja
Pohjois-Makedonia
Portugali
Puola
Ranska
Romania
Ruotsi
Saksa
San Marino
Serbia
Slovakia
Slovenia
Suomi
Sveitsi
Tanska
Tsekin tasavalta
Ukraina
Unkari
Valko-Venäjä
Vatikaanivaltio
Venäjä
Viro
Yhdistynyt kuningaskunta