60 Hz Standby Range (kW/kVA) 1590-2000/1988-2500
60 Hz Prime Range (kW/kVA) 1440-1820/1800-2275
- Frequency 60 Hz (Available in 50 Hz)
- Speed 1800 RPM (1500 RPM for 50 Hz)
- Alternator Type Brushless, Rare-Earth, Permanent-Magnet
- Engine Manufacturer Kohler
- Emissions US EPA (Certified) Stationary Emergency
Features:
- KOHLER Co. provides one-source responsibility for the generating system and accessories.
- The generator set and its components are prototype-tested, factory-built, and production-tested.
- The 60 Hz generator set offers a UL 2200 listing.
- The generator set accepts rated load in one step.
- The 60 Hz generator set meets NFPA 110, Level 1, when equipped with the necessary accessories and installed per NFPA standards.
- A standard one-year limited warranty covers all systems and components. Two-, five-, and ten-year extended warranties are also available.
Alternator features:
- The pilot-excited, permanent-magnet (PM) alternator provides superior short-circuit capability.
- The brushless, rotating-field alternator has broad range reconnectability.
- Additional alternator voltages are available including 12.47 kV, 13.2 kV, and 13.8 kV medium voltages. Contact your local distributor for details.
- NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting.
- Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.
- Sustained short-circuit current enabling down stream circuit breakers to trip without collapsing the alternator field.
- Self-ventilated and drip-proof construction.
- Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
- Digital solid-state, volts-per-hertz voltage regulator with ±0.25% no-load to full-load regulation.
- Brushless alternator with brushless pilot exciter for excellent load response.
Other features:
- KOHLER-designed controllers for guaranteed system integration and remote communication.
- The low coolant level shutdown prevents overheating (standard on radiator models only).
- An electronic, isochronous governor delivers precise frequency regulation.
- Multiple circuit breaker configurations.