Model Number HQP7-1; HQP7-2; HQP7-MDU-1; HQP7-MDU-2
Power Processor (P): 24–36 V- 250 mA
Links (L1 / L2): 24–36 V- 2 A per link
Typical Power
Consumption
4.2 W; 8 Power Draw Units (PDUs)
Test conditions: Two Ethernet links connected, both device links in use
Regulatory Approvals cULus, NOM
Environment Indoor use only. 32 °F to 104 °F (0 °C to 40 °C), 0% to 90% humidity,
non-condensing
Heat Generated 15 BTU/hr — typical
(24 BTU/hr with 2 links at 2 A each output)
Cooling Method Passive Cooling
Power Failure Memory System data stored in non-volatile memory. Timeclock retention for 10 years
Internal Timeclock ±1 minute per year
Miswire Protection All terminal block inputs are over-voltage and miswire protected against wire
reversals and shorts
Low-Voltage Link
Wire Type
Two pair — one pair 18 AWG (0.75 mm2), one pair 18 to 22 AWG
(0.34 to 0.75 mm2) twisted shielded — IEC PELV / NEC® Class 2 cable
Low-Voltage Power
Wire Type
18 AWG (0.75 mm2)
Communications Ethernet, RS485 (QS, RF)
Link Capacities HomeWorks QS Wired Device Link 99 devices/512 zones
HomeWorks Clear Connect - Type A Link 99 devices/100 zones
ESD Protection Meets or exceeds the IEC 61000-4-2 standard
Surge Protection Meets or exceeds ANSI/IEEE C62.41 standard
Mounting Mounts in HQ-LV21, L-LV14, L-LV21, or PDx- control panel
Dimensions With terminal blocks (as shown): 4.25 in (108 mm) x 3.94 in (100 mm)
Without terminal blocks: 4.25 in (108 mm) x 3.54 in (90 mm)
Connections 4-pin removable terminal blocks. 1 for HQP7-1, 2 for HQP7-2.
One 4-pin removable terminal block* for Power Input.
Two RJ45 standard Ethernet connections.
*Each terminal will accept up to two 18 AWG (0.75 mm2) wires.