*Updated 2021* The CEPC senses a local, single normal power circuit. As long as
normal power is present, the CEPC permits normal and emergency
switching of the lighting load from Cooper Lighting Solutions
lighting control panels or occupancy sensors. If normal power is lost
for any reason, the CEPC will force the connected emergency
fixtures ON. The CEPC can be wired as either a control device along
with a relay panel and occupancy sensor, or as a shunt to bypass
line voltage devices when normal power fails. The CEPC-2-D is a
universally compatible device that allows control of 4-wire
emergency dimming loads. When normal power is lost, the CEPC-2-
D will force the emergency fixtures to the full bright condition. Both
CEPC models include a test switch feature for verifying proper
functionality.